We also provide item sourcing and flight consolidation solutions. We have now our very own manufacturing facility and sourcing place of work. We could provide you with nearly every kind of merchandise associated to our merchandise variety for Central Air Installation, Vision Inspection Systems, gas power piping projects, Our tenet is "Reasonable prices, efficient production time and best service" We hope to cooperate with more customers for mutual development and benefits.
China Supplier Central Air System - Circulating air system pressure difference control – TekMax Detail:

Measures taken to maintain differential pressure:

In general, the air supply system adopts more methods of constant air volume, that is, firstly, ensure that the air volume of the clean room is relatively constant, and adjust the return air volume or exhaust air volume of the clean room to control the pressure difference air volume of the clean room and maintain the pressure difference of the clean room. value. Install a manual split multi-leaf regulating valve or butterfly valve on the clean room return and exhaust branch pipes to adjust the return and exhaust air volume and control the indoor pressure difference. Adjust the pressure difference in the clean room when the air conditioning system is debugged. During the operation of the air conditioning system, when the pressure difference in the clean room deviates from the set value, it will be more troublesome to adjust. Install a damping layer (such as single-layer non-woven fabric, stainless steel filter, aluminum alloy filter, nylon filter, etc.) at the return (exhaust) air outlet of the clean room, which can effectively ensure the positive pressure of the clean room, but it needs to be replaced frequently. The filter screen of the damping layer prevents the positive pressure in the clean room from being too high. Install a residual pressure valve on the wall between adjacent rooms to control the positive pressure. The advantage is that the equipment is simple and reliable, but the disadvantage is that the residual pressure valve has a relatively large size, limited ventilation, inconvenient installation, and inconvenient connection with the air duct. Install an electric actuator system on the valve shaft of the clean room return (exhaust) air branch control valve, so as to form an electric control valve with the corresponding valve. According to the feedback of the pressure difference in the clean room, fine-tune the valve opening, and automatically adjust the pressure difference in the clean room to return to the set value. This method is more reliable and accurate for controlling the pressure difference in the clean room, and is widely used in engineering practice. The system can be installed in the clean room that needs to display the pressure difference or the return (exhaust) air branch control valve of the typical clean room.

Venturi air volume control valves are installed on the air supply branch pipe and the return (exhaust) air branch pipe of the clean room. There are three types of venturi valves-constant air volume valve, which can provide stable air flow; bistable valve, which can provide two different air flow, namely maximum and minimum flow; variable air volume valve, which can pass the command less than 1 Second response and flow feedback signal closed loop control air flow.

Venturi valve has the characteristics of being unaffected by changes in air duct pressure, quick response (less than 1 second), precise adjustment, etc., but the equipment is relatively expensive, and it is suitable for applications where the system pressure difference control must be high-precision and high-reliability.

Through the use of constant air volume valves and bistable valves, the air supply and exhaust volume of the clean room can be strictly controlled, so as to form a stable pressure difference air volume and control the pressure difference of the clean room to be stable.

The air supply variable air volume valve is used to adjust the room, so that the flow of the air supply pipe valve can track the flow of the exhaust pipe valve, which can form a stable differential air volume and control the stable pressure of the clean room.

Use the supply air fixed air volume valve and the return air variable air volume valve to control the room, so that the return air valve can track the change of the room pressure difference and automatically adjust the room pressure difference to form a stable pressure difference air volume and control the clean room pressure difference stability.


Product detail pictures:

China Supplier Central Air System - Circulating air system pressure difference control – TekMax detail pictures


Related Product Guide:

We aim to find out quality disfigurement from the production and supply the best service to domestic and overseas customers wholeheartedly for China Supplier Central Air System - Circulating air system pressure difference control – TekMax , The product will supply to all over the world, such as: Czech Republic, Casablanca, Spain, Our products are mainly exported to Southeast Asia, the Middle East, North America and Europe. Our quality is surely guaranteed. If you are interested in any of our products or would like to discuss a custom order, please feel free to contact us. We are looking forward to forming successful business relationships with new clients around the world in the near future.
  • The company comply with the contract strict, a very reputable manufacturers, worthy a long-term cooperation.
    5 Stars By Georgia from Atlanta - 2018.03.03 13:09
    It is really lucky to meet such a good supplier, this is our most satisfied cooperation, I think we will work again!
    5 Stars By Victoria from Zimbabwe - 2018.10.31 10:02
    Write your message here and send it to us