We retain bettering and perfecting our goods and service. At the same time, we perform actively to do research and enhancement for Clean Room, Sterilization And Sterilization, Insulation System Maintenance Framework, Standing still today and looking into the future, we sincerely welcome customers all over the world to cooperate with us.
High Quality for Ductless Air - Circulating air system pressure difference control – TekMax Detail:

Measures taken to maintain differential pressure:

In general, the air supply system adopts more methods of constant air volume, that is, firstly, ensure that the air volume of the clean room is relatively constant, and adjust the return air volume or exhaust air volume of the clean room to control the pressure difference air volume of the clean room and maintain the pressure difference of the clean room. value. Install a manual split multi-leaf regulating valve or butterfly valve on the clean room return and exhaust branch pipes to adjust the return and exhaust air volume and control the indoor pressure difference. Adjust the pressure difference in the clean room when the air conditioning system is debugged. During the operation of the air conditioning system, when the pressure difference in the clean room deviates from the set value, it will be more troublesome to adjust. Install a damping layer (such as single-layer non-woven fabric, stainless steel filter, aluminum alloy filter, nylon filter, etc.) at the return (exhaust) air outlet of the clean room, which can effectively ensure the positive pressure of the clean room, but it needs to be replaced frequently. The filter screen of the damping layer prevents the positive pressure in the clean room from being too high. Install a residual pressure valve on the wall between adjacent rooms to control the positive pressure. The advantage is that the equipment is simple and reliable, but the disadvantage is that the residual pressure valve has a relatively large size, limited ventilation, inconvenient installation, and inconvenient connection with the air duct. Install an electric actuator system on the valve shaft of the clean room return (exhaust) air branch control valve, so as to form an electric control valve with the corresponding valve. According to the feedback of the pressure difference in the clean room, fine-tune the valve opening, and automatically adjust the pressure difference in the clean room to return to the set value. This method is more reliable and accurate for controlling the pressure difference in the clean room, and is widely used in engineering practice. The system can be installed in the clean room that needs to display the pressure difference or the return (exhaust) air branch control valve of the typical clean room.

Venturi air volume control valves are installed on the air supply branch pipe and the return (exhaust) air branch pipe of the clean room. There are three types of venturi valves-constant air volume valve, which can provide stable air flow; bistable valve, which can provide two different air flow, namely maximum and minimum flow; variable air volume valve, which can pass the command less than 1 Second response and flow feedback signal closed loop control air flow.

Venturi valve has the characteristics of being unaffected by changes in air duct pressure, quick response (less than 1 second), precise adjustment, etc., but the equipment is relatively expensive, and it is suitable for applications where the system pressure difference control must be high-precision and high-reliability.

Through the use of constant air volume valves and bistable valves, the air supply and exhaust volume of the clean room can be strictly controlled, so as to form a stable pressure difference air volume and control the pressure difference of the clean room to be stable.

The air supply variable air volume valve is used to adjust the room, so that the flow of the air supply pipe valve can track the flow of the exhaust pipe valve, which can form a stable differential air volume and control the stable pressure of the clean room.

Use the supply air fixed air volume valve and the return air variable air volume valve to control the room, so that the return air valve can track the change of the room pressure difference and automatically adjust the room pressure difference to form a stable pressure difference air volume and control the clean room pressure difference stability.


Product detail pictures:

High Quality for Ductless Air - Circulating air system pressure difference control – TekMax detail pictures


Related Product Guide:

We've our have sales staff, style and design staff, technical crew, QC team and package workforce. We've strict excellent control procedures for each system. Also, all of our workers are experienced in printing field for High Quality for Ductless Air - Circulating air system pressure difference control – TekMax , The product will supply to all over the world, such as: Johannesburg, Salt Lake City, Kuwait, Products have been exported to Asia, Mid-east,European and Germany market. Our company has constantly been able to update the products performance and safety to meet the markets and strive to be top A on stable quality and sincere service. If you have the honor to do business with our company. we will definitely do our very best to support your business in China.
  • High production efficiency and good product quality, fast delivery and completed after-sale protection, a right choice, a best choice.
    5 Stars By Evelyn from Italy - 2017.06.16 18:23
    The enterprise has a strong capital and competitive power, product is sufficient, reliable, so we have no worries on cooperating with them.
    5 Stars By John biddlestone from Turkmenistan - 2018.09.21 11:44
    Write your message here and send it to us