I、Temperature:
Celsius (C) and Fahrenheit (F)
Fahrenheit = 32 + Celsius × 1.8
Celsius = (Fahrenheit -32) /1.8
Kelvin (K) and Celsius (C)
Kelvin (K) = Celsius (C) +273.15
II、Pressure conversion:
Mpa、Kpa、pa、bar
1Mpa=1000Kpa;
1Kpa=1000pa;
1Mpa=10bar;
1bar=0.1Mpa=100Kpa;
1atmospher=101.325Kpa=1bar=1Kilogram;
1bar=14.5psi;
1psi=6.895Kpa;
1 kg/cm2=105=10 mH2O=1 bar=0.1 MPa
1 Pa=0.1 mmH2O=0.0001 mH2O
1 mH2O=104 Pa=10 kPa
III、Wind speed, volume conversion
1CFM =1.699 M³/H=0.4719 l/s
1M³/H=0.5886CFM
1l/s=2.119CFM
1FPM=0.3048 m/min=0.00508 m/s
IV、Cooling capacity and power:
1KW=1000 W
1KW=861Kcal/h=0.39 P(cooling capacity)
1W= 1 J/s
1USTR=3024Kcal/h=3517W(cooling capacity)
1BTU=0.252kcal/h=1055J
1BTU/H=0.252kcal/h
1BTU/H=0.2931W(cooling capacity)
1MTU/H=0.2931KW(cooling capacity)
1HP(electricity)=0.75KW(electricity)
1KW(electricity)=1.34HP(electricity)
1RT(cooling capacity)=3.517KW(cooling capacity)
1KW(cooling capacity)=3.412MBH
1P(cooling capacity)=2200kcal/h=2.56KW
1kcal/h=1.163W
V、Air conditioning installation thickness and cooling capacity:
1.5mm2=12A-20A(2650~4500W) 1P~2P
2.5mm2=20-25A(4500~5500W) 2P
4mm2=25-32A(5500~7500W) 2P~3P
6mm2=32-40A(7500~8500W) 3P~4P
VI、Refrigerant calculation formula:
1、Selection of expansion valve: cold ton + 1.25% allowance
2、Press power: 1P= 0.735kW
3、Refrigerant charge: Cooling capacity (KW) ÷3.516 x 0.58
4、Water flow of air cooler: Cooling capacity (KW) ÷ temperature difference ÷1.163
5、Cooling water flow rate of water-cooled screw machine: Cooling capacity (KW) ×0.86÷ temperature difference
6、Cooling water flow rate of water-cooled screw machine cooling capacityKW+ press power) ×0.86÷ temperature difference
7、Gross heating value QT=QS+QL
8、Air cooling:QT =0.24*∝*L*(h1-h2)
9、Significant heat air cooling:QS=Cp*∝*L*(T1-T2)
10、Latent heat of air cooling:QL=600*∝*L*(W1-W2)
11、Freezing water volume:L/sV1= Q1/(4.187△T1)
12、Cooling water volume:L/sV2=Q2/(4.187△T2)=(3.516+KW/TR)TR,Q2=Q1+N=TR*3.516+KW/TR*TR=(3.516+KW/TR)*TR
13、Refrigeration efficiency: EER= Refrigeration capacity (Mbtu/h)/power consumption (KW); COP= Refrigeration capacity (KW)/power consumption (KW)
14、Partial cooling load performance:NPLV=1/(0.01/A+0.42/B+0.45/C+0.12/D)
15、Full load current (three phase):FLA=N/√3 UCOSφ
16、Fresh air volume:Lo=nV
17、Air supply volume:L=Qs/〔Cp*∝*(T1-T2)〕
18、Power of fan:N1=L1*H1/(102*n1*n2)
19、Power of the water pump:N2= L2*H2*r/(102*n3*n4)
20、The pipe diameter:D=√4*1000L2/(π*v)
21、Duct area:F=a*b*L1/(1000u)